BH 0.66 Protective Current Transformer Selection Guide

10, Nov. 2026

 

BH 0.66 Protective Current Transformer Selection Guide

To select a BH 0.66 protective current transformer, first confirm the system voltage and current ratio, then match the protection relay’s secondary input, required protection accuracy, rated burden, and installation dimensions. “0.66” commonly identifies a 0.66 kV application, but buyers should verify the exact meaning and rated values against the product nameplate and supplier drawings. At ANNEZEE, we recommend confirming these details before requesting a quotation so the proposed transformer suits the switchgear, relay, and protection scheme rather than only matching a product label.

View Details

Who This Guide Is For

This guide is for electrical equipment manufacturers, panel builders, EPC contractors, distributors, and industrial buyers evaluating a BH 0.66 protective current transformer. It is intended to support early technical screening and RFQ preparation, not to replace an engineer’s protection study or the applicable installation requirements. Use it when comparing product options, checking compatibility, or preparing a specification for supplier review.

How a Protective Current Transformer Fits a System

A current transformer (CT) converts a high primary current into a lower secondary current that can be measured by a protection relay or other connected instrument. A protective CT is selected to provide a suitable signal to protection equipment during operating conditions relevant to the protection scheme. The CT’s ratio, accuracy class, burden, and saturation performance all affect whether it can serve the intended application.

A BH 0.66 model is generally considered for low-voltage systems with a rated voltage associated with 0.66 kV. That voltage designation alone does not define the CT’s current ratio, accuracy, burden, or physical fit. Treat each of those as a separate requirement and verify it in the manufacturer’s technical documentation.

Types, Materials, and Specification Options

Core and winding considerations

Protective CTs use a magnetic core and primary and secondary windings to transfer a current signal. Core characteristics influence how the CT behaves under fault-current conditions, so protection applications require attention to the specified protection class and performance rather than choosing a unit solely by ratio. Ask the supplier to identify the offered construction and the relevant performance data in the datasheet.

Housing, insulation, terminal arrangement, and mounting style may vary by product design. These features affect installation and integration, but should not be assumed from the BH 0.66 designation. Request dimensional drawings and connection details for the exact model under consideration.

Key specifications to confirm

Specification What to check Why it matters
Rated voltage Confirm the 0.66 kV system application and product insulation details Establishes whether the unit is suitable for the intended electrical system
Current ratio Specify primary and secondary current, such as 200/5 A if required by the design Must align with the circuit current and relay input settings
Protection class State the class and any required accuracy-limit or saturation parameters Supports relay operation under the conditions defined by the protection study
Rated burden Provide the connected relay, lead, and other relevant load information in VA Helps confirm that the CT can drive its connected secondary circuit as specified
Frequency Confirm whether the application is 50 Hz or 60 Hz The selected unit should match the system frequency stated in the project specification
Installation Check dimensions, aperture, mounting, terminals, and conductor arrangement Prevents fit and wiring issues during panel assembly or replacement

The example ratio of 200/5 A is illustrative, not a recommendation for every project. Secondary ratings such as 1 A and 5 A are common options in CT systems, but the correct choice depends on the relay, wiring, and system design. Likewise, 50 Hz and 60 Hz are system frequency options to confirm, not interchangeable assumptions.

Match the CT to Its Application

Typical applications to evaluate include low-voltage switchboards, motor feeders, distribution panels, and protection circuits where a compatible CT signal is required. The appropriate configuration depends on the circuit current, the relay’s input requirements, available installation space, and the intended protection function. For replacement projects, compare the existing nameplate and installation arrangement with the new unit’s full documentation.

For a feeder protection application, start with the relay and protection design requirements, then confirm the CT ratio and protection performance. For a panel OEM or equipment manufacturer, also check how the CT fits the busbar or conductor arrangement and how its terminals will be accessed. In either case, the supplier should review the application details rather than infer them from “BH 0.66” alone.

A Practical Selection Framework

Step 1: Define the electrical system

Record the system voltage, frequency, maximum operating current, and expected fault conditions provided by the project engineer. Confirm that the required nominal voltage is 0.66 kV where applicable, and do not treat the designation as proof of every insulation or operating parameter. Include the circuit’s earthing and protection context when relevant to the technical review.

ANNEZEE contains other products and information you need, so please check it out.

Step 2: Align ratio and secondary input

Specify the required primary-to-secondary ratio and whether the connected relay expects a 1 A or 5 A input. Check the relay documentation and system design before settling on a secondary rating. If the CT is replacing an installed unit, record the existing ratio and verify that the relay configuration will remain appropriate.

Step 3: Confirm protection performance and burden

Ask the protection engineer to identify the required protection class and performance parameters for the fault levels and relay scheme. Calculate or provide the secondary circuit burden, including connected devices and lead contribution where required by the design. Have the supplier confirm the offered CT data against those requirements; do not choose a class or burden by guesswork.

Step 4: Check fit, wiring, and documentation

Compare the product outline drawing with the available space, conductor dimensions, mounting points, and terminal orientation. Confirm the wiring diagram, polarity markings, and terminal identification before installation. Review the datasheet and any project-specific documents to ensure the quotation and supplied product refer to the same configuration.

Pricing, MOQ, and Lead Time

Price and availability can depend on the required ratio, protection class, burden, mechanical configuration, order quantity, and requested documentation. Custom or project-specific requirements may affect production planning, so a generic product description is not enough to establish a firm price or delivery date. We recommend sending the full technical specification and target quantity for a configuration-specific quotation.

Minimum order quantity (MOQ) and lead time should be confirmed with the supplier for the particular model and order conditions. If the project has a delivery deadline, state the required delivery location and schedule when requesting a quote. Ask whether the quoted lead time begins after technical approval, order confirmation, or another defined milestone.

Supplier Evaluation Checklist

  • Can the supplier provide a datasheet and dimensional drawing for the exact BH 0.66 configuration?
  • Does the offer state the ratio, secondary rating, protection class, burden, and frequency?
  • Can the supplier review the relay requirements and application information you provide?
  • Are terminal markings, polarity, mounting details, and connection information documented?
  • Are MOQ, production lead time, quotation validity, and shipping terms clearly stated?
  • Can the supplier identify any deviations between your specification and the offered product?

Clear answers make technical comparisons more useful than comparing unit price alone. Request written confirmation of any exceptions, particularly if a project requires specific drawings, labeling, packaging, or inspection documentation. Do not assume that a standard offer includes requirements that are not listed in the quotation.

Common Selection Mistakes to Avoid

A frequent mistake is selecting by voltage designation and ratio alone while overlooking the protection class, burden, or relay input. Another is assuming that the existing CT can be replaced with a physically similar model without checking its full nameplate and connection details. Buyers should also avoid treating illustrative specification examples as project recommendations.

Installation and commissioning should be handled by qualified personnel following the applicable equipment instructions and project safety procedures. A CT secondary circuit should be managed according to the manufacturer’s instructions and the relevant electrical practices; do not alter wiring based only on a product listing. Where system data or protection requirements are unclear, obtain an engineering review before purchase.

Summary and Next Steps

The right BH 0.66 protective current transformer is the one whose rated voltage, current ratio, secondary rating, protection performance, burden, frequency, and physical design match the project. The 0.66 kV designation is only a starting point; it does not provide enough information to finalize selection. Confirm the complete specification with the relay documentation, installation drawings, and protection design.

To move forward, prepare the system voltage and frequency, required ratio, relay model or input rating, protection class, burden, installation dimensions, quantity, and delivery target. ANNEZEE can review these details and provide a product configuration and quotation for evaluation. Send your project requirements to our sales team to begin a technical discussion and confirm availability, MOQ, and lead time.

Want more information on BH 0.66 Protective Current Transformer? Feel free to contact us.